问题描述

风扇 报告严重的示例

  • DS460C

Wed Mar 09 11:43:31 -0500 [NODE03: dsa_worker4: ses.status.fanError:EMERGENCY]: DS460-12 (S/N SHJGXXXXXXXX) shelf 1 on channel 0a cooling fan error for Cooling element 3: critical status; fan is off. This module is on the rear of the shelf to the left.

Wed Mar 09 11:43:31 -0500 [NODE03: dsa_worker4: callhome.shlf.fan:EMERGENCY]: Call home for SHELF COOLING UNIT FAILED
 
Wed Mar 09 11:43:40 -0500 [NODE04: statd: monitor.shelf.fault:alert]: Critical fault reported on disk storage shelf attached to channel 0a. Check fans, power supplies, disks, and temperature sensors.
Wed Mar 09 11:43:40 -0500 [NODE04: statd: callhome.shlf.fault:error]: Call home for SHELF_FAULT

NS224:巴西

Mon Mar 14 09:13:52 +0900 [Node01: dsa_worker1: ses.status.fanError:EMERGENCY]: NS224NSM100 (S/N SHFNxxxxxx) shelf 0 on channel 0x cooling fan error for Cooling element 15: critical status; fan is off. This element is on the unknown location.

Mon Mar 14 09:13:52 +0900 [Node01: dsa_worker1: callhome.shlf.fan:EMERGENCY]: Call home for SHELF COOLING UNIT FAILED

  •   DS2246 

Wed Mar 13 14:57:10 +0530 [rpsdlxx1: dsa_worker4: ses.status.temperatureInfo:info]: DS2246 (S/N SHFFG1451000046) shelf 12 on channel 0a temperature information for Temperature sensor 4: normal status.

Wed Mar 13 15:00:00 +0530 [rpsdlxx1: statd: monitor.shelf.fault:alert]: Critical fault reported on disk storage shelf attached to channel 0a. Check fans, power supplies, disks, and temperature sensors.

 

  • STORAGE-FAULT 显示风扇状态 CRITICAL
Fans:
Element Status         Status Bytes  Status Descriptions
1: OK                01,05,16,A7
2: OK                01,04,50,A5
3: CRITICAL          02,01,BC,A1
4: OK                01,04,68,A5
5: OK                01,05,0D,A6
6: OK                01,04,47,A5
7: OK                01,04,74,A5
8: OK                01,04,5C,A5
  • ENVIRONMENT 显示RPM异常:
Cooling Unit installed element list: 1, 2, 3, 4, 5, 6, 7, 8; with error: 3
Cooling Units by element:
[1] 12840 RPM
[2] 11160 RPM
[3] 0 RPM
[4] 11130 RPM
[5] 12990 RPM
[6] 10950 RPM
[7] 11340 RPM
[8] 11160 RPM
  • 重新安装风扇不能解决这种情况