由于出现"电源故障"错误、节点重新启动

i
Knowledge Base guidance

This article may include metadata, visibility, validation state, and related support guidance.

适用场景

  • AFF FAS8200或 FAS2620  / FAS2650
  • FAS2720/FAS2750
  • AF-A220

问题描述

  • Node console或SP/BMC> system log或 输出显示节点因"Power Fail"(电源故障)错误而重新启动。

示例 (重新启动): 

****************************
* Power Fail - Please Wait *
****************************
...
Destage is in progress, please wait
..........................................
Destage is completed successfully
Powering off from the backup power source
:
Waiting for giveback...(Press Ctrl-C to abort wait)

示例 (启动循环):

****************************
* Power Fail - Please Wait *
****************************
...
Destage is in progress, please wait
..........................................
Destage is completed successfully
Powering off from the backup power source
BIOS Version: 11.2.1
Portions Copyright (C) 2014-2018 NetApp, Inc. All Rights Reserved.
...
Initializing System Memory ...
Loading Device Drivers ...
BIOS Version: 11.2.1
Portions Copyright (C) 2014-2018 NetApp, Inc. All Rights Reserved.
Initializing System Memory ...
Loading Device Drivers ...

  • 节点 SP/BMC events all报告:

Record 1234: Mon Jan  1 00:01:01 2024 [SP.emergency]: System input power lost
Record 2345: Mon Jan  1 00:10:10 2024 [SP.emergency]: System input power lost

  • 任何电源设备(PSU)、配电设备(PDU) 或任何其他数据中心电气 元件(磁盘架、交换机等)均不报告任何其他电源警报