DS460磁盘架显示风扇不可用

i
Knowledge Base guidance

This article may include metadata, visibility, validation state, and related support guidance.

适用场景

DS460-12磁盘架

问题描述

  • 受影响磁盘架在环境中显示以下风扇状态:

::> system node run -node <nodename> -command environment status

Cooling Units by element:
[1] 5100 RPM
[2] 4500 RPM
[3] 5070 RPM
[4] 4500 RPM
[5] Unavailable<--
[6] Unavailable<--
[7] Unavailable<--
[8] Unavailable<--
 
  • EMS日志显示以下消息
[Node-01: dsa_disc: ses.status.fanError:EMERGENCY]: DS460-12 (S/N XXXXXXXX) shelf X on channel 2d cooling fan error for Cooling element 8 7 6 5: critical status no redundancy. This module is on the rear of the shelf to the right.
[Node-01: dsa_disc: ses.status.fanError:EMERGENCY]: DS460-12 (S/N XXXXXXXX) shelf X on channel 2d cooling fan error for Cooling element 8 7 6 5: critical status no redundancy. This module is on the rear of the shelf to the right.
  • 存储故障对于风扇元素状态显示"未安装"、类似于以下内容:

::> system node run -node <nodename> -command storage show fault -v

...
Fans:
Element Status         Status Bytes  Status Descriptions
  1: OK                01,05,13,A6
  2: OK                01,04,41,A5
  3: OK                01,04,4A,A5
  4: OK                01,04,56,A5
  5: NOT INSTALLED     05,00,00,20
  6: NOT INSTALLED     05,00,00,20
  7: NOT INSTALLED     05,00,00,20
  8: NOT INSTALLED     05,00,00,20

  • 已更换风扇模块、但问题描述仍然存在