适用场景

  • 集群网络交换机
  • Cisco C9336C
  • 电源( PSU )

问题描述

  • 有关交换机 PSU 故障的 ONTAP EMS 通知:
HA Group Notification (Health Monitor process cshm: SwitchFanUnknown_Alert[sw02(serial_number)/PowerSupply-1 Fan-1]) ALERT
 
  • 交换机日志 `show environment` 确认损坏的 PSU :
`show environment`
Fan:
---------------------------------------------------------------------------
Fan Model Hw Direction Status
---------------------------------------------------------------------------
Fan1(sys_fan1) NXA-FAN-65CFM-PE -- back-to-front Ok
Fan2(sys_fan2) NXA-FAN-65CFM-PE -- back-to-front Ok
Fan3(sys_fan3) NXA-FAN-65CFM-PE -- back-to-front Ok
Fan_in_PS1 -- -- back-to-front None
Fan_in_PS2 -- -- back-to-front Ok
Fan Zone Speed: Zone 1: 0xb3
Fan Air Filter : NotSupported
 
电源:
Voltage: 12 Volts
Power Actual Actual Total
Supply Model Output Input Capacity Status
(Watts ) (Watts ) (Watts )
------- ---------- --------------- ------ ---------- --------------------
1 NXA-PAC-1100W-PE2 0 W 0 W 0 W Fail/Shut
2 NXA-PAC-1100W-PE2 280 W 298 W 1100 W Ok
 
  • 电源线和电源连接正常